CVE-2026-2405 1 Schneider-electric 1 Powerchute Serial Shutdown 2026-04-22 6.5 Medium
CWE-400 Uncontrolled Resource Consumption vulnerability exists that could cause excessive troubleshooting zip file creation and denial of service when a Web Admin user floods the system with POST /helpabout requests.
CVE-2026-1227 1 Schneider-electric 2 Ecostruxure Building Operation Webstation, Ecostruxure Building Operation Workstation 2026-04-17 N/A
CWE-611: Improper Restriction of XML External Entity Reference vulnerability exists that could cause unauthorized disclosure of local files, interaction within the EBO system, or denial of service conditions when a local user uploads a specially crafted TGML graphics file to the EBO server from Workstation.
CVE-2026-1226 1 Schneider-electric 2 Ecostruxure Building Operation Webstation, Ecostruxure Building Operation Workstation 2026-04-17 N/A
CWE‑94: Improper Control of Generation of Code vulnerability exists that could cause execution of untrusted or unintended code within the application when maliciously crafted design content is processed through a TGML graphics file.
CVE-2026-4832 1 Schneider-electric 25 Easergy P14x, Easergy P24x, Easergy P341 and 22 more 2026-04-17 N/A
CWE-798 Use of Hard-coded Credentials vulnerability exists that could cause unauthorized access to sensitive device information when an unauthenticated attacker is able to interrogate the SNMP port.
CVE-2026-1286 1 Schneider-electric 2 Ecostruxure Foxboro Dcs Control Software, Foxboro Dcs 2026-04-17 6.5 Medium
CWE-502: Deserialization of untrusted data vulnerability exists that could lead to loss of confidentiality, integrity and potential remote code execution on workstation when an admin authenticated user opens a malicious project file.
CVE-2026-2273 1 Schneider-electric 1 Ecostruxure Automation Expert 2026-04-17 8.2 High
CWE-94: Improper Control of Generation of Code ('Code Injection') vulnerability exist that could cause execution of untrusted commands on the engineering workstation which could result in a limited compromise of the workstation and a potential loss of Confidentiality, Integrity and Availability of the subsequent system when an authenticated user opens a malicious project file.
CVE-2024-8935 1 Schneider-electric 3 Modicon M340 Bmxp341000, Modicon Mc80 Bmkc8020301, Modicon Momentum Unity M1e Processor 2026-04-15 7.5 High
CWE-290: Authentication Bypass by Spoofing vulnerability exists that could cause a denial of service and loss of confidentiality and integrity of controllers when conducting a Man-In-The-Middle attack between the controller and the engineering workstation while a valid user is establishing a communication session. This vulnerability is inherent to Diffie Hellman algorithm which does not protect against Man-In-The-Middle attacks.
CVE-2024-8933 1 Schneider-electric 3 Modicon M340, Modicon Mc80, Modicon Momentum Unity M1e Processor 2026-04-15 7.5 High
CWE-924: Improper Enforcement of Message Integrity During Transmission in a Communication Channel vulnerability exists that could cause retrieval of password hash that could lead to denial of service and loss of confidentiality and integrity of controllers. To be successful, the attacker needs to inject themself inside the logical network while a valid user uploads or downloads a project file into the controller.
CVE-2025-9996 1 Schneider-electric 1 Blmon 2026-04-15 N/A
CWE-78: Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') vulnerability exists that could cause the execution of any shell command when executing a netstat command using BLMon Console in an SSH session.
CVE-2025-9997 1 Schneider-electric 1 Blmon 2026-04-15 N/A
CWE-78: Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') vulnerability exists that could cause command injection in BLMon that is executed in the operating system console when in a SSH session.
CVE-2025-8448 1 Schneider-electric 2 Ecostruxure Building Operation Enterprise Server, Ecostruxure Workstation 2026-04-15 N/A
CWE-200: Exposure of Sensitive Information to an Unauthorized Actor vulnerability exists that could cause unauthorized access to sensitive credential data when an attacker is able to capture local SMB traffic between a valid user within the BMS network and the vulnerable products.
CVE-2025-8449 1 Schneider-electric 3 Ecostruxure Building Operation Enterprise Server, Ecostruxure Enterprise Server, Ecostruxure Workstation 2026-04-15 N/A
CWE-400: Uncontrolled Resource Consumption vulnerability exists that could cause a denial of service when an authenticated user sends a specially crafted request to a specific endpoint from within the BMS network.
CVE-2025-8453 1 Schneider-electric 2 Saitel Dp, Saitel Dr 2026-04-15 6.7 Medium
CWE-269: Improper Privilege Management vulnerability exists that could cause privilege escalation and arbitrary code execution when a privileged engineer user with console access modifies a configuration file used by a root-level daemon to execute custom scripts.
CVE-2025-7746 1 Schneider-electric 1 Altivar 2026-04-15 N/A
CWE-79: Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') vulnerability exists that could cause an unvalidated data injected by a malicious user potentially leading to modify or read data in a victim’s browser.
CVE-2025-6625 1 Schneider-electric 12 Bmxngd0100, Bmxngd0100 Firmware, Bmxnoc0401 and 9 more 2026-04-15 7.5 High
CWE-20: Improper Input Validation vulnerability exists that could cause a Denial Of Service when specific crafted FTP command is sent to the device.
CVE-2025-54923 1 Schneider-electric 2 Ecostruxure Power Monitoring Expert, Ecostruxure Power Operation With Advanced Reports 2026-04-15 N/A
CWE-502: Deserialization of Untrusted Data vulnerability exists that could cause remote code execution and compromise of system integrity when authenticated users send crafted data to a network-exposed service that performs unsafe deserialization.
CVE-2025-54924 1 Schneider-electric 2 Ecostruxure Power Monitoring Expert, Ecostruxure Power Operation With Advanced Reports 2026-04-15 7.5 High
CWE-918: Server-Side Request Forgery (SSRF) vulnerability exists that could cause unauthorized access to sensitive data when an attacker sends a specially crafted document to a vulnerable endpoint.
CVE-2025-54925 1 Schneider-electric 2 Ecostruxure Power Monitoring Expert, Ecostruxure Power Operation With Advanced Reports 2026-04-15 7.5 High
CWE-918: Server-Side Request Forgery (SSRF) vulnerability exists that could cause unauthorized access to sensitive data when an attacker configures the application to access a malicious url.
CVE-2025-54926 1 Schneider-electric 2 Ecostruxure Power Monitoring Expert, Ecostruxure Power Operation With Advanced Reports 2026-04-15 7.2 High
CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists that could cause remote code execution when an authenticated attacker with admin privileges uploads a malicious file over HTTP which then gets executed.
CVE-2025-54927 1 Schneider-electric 2 Ecostruxure Power Monitoring Expert, Ecostruxure Power Operation With Advanced Reports 2026-04-15 4.9 Medium
CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists that could cause unauthorized access to sensitive files when an authenticated attackers uses a crafted path input that is processed by the system.